| Residential and small commercial wiring | Usually up to 450/750 V or 0.6/1 kV, depending on the installation system | Copper or aluminium conductor with flame-retardant thermoplastic or low-smoke, halogen-free insulation and sheath | Limited flame spread; low smoke and low corrosive gas are preferred in occupied buildings and escape routes | IEC 60332-1-2; IEC 60754-1 and IEC 60754-2 where halogen-free performance is required; IEC 61034-2 for smoke density | Confirm conductor size, current-carrying capacity, voltage rating, ambient temperature, grouping, and installation method |
| Cable trays and shared service areas | Commonly 0.6/1 kV for building services, industrial distribution, and control circuits | Multicore cable with flame-retardant sheath; use a screened or armoured design when electromagnetic protection or mechanical protection is needed | Use a bunch or vertical-tray flame test rather than relying only on a single-cable flame test; low smoke helps maintain visibility | IEC 60332-3-23 or IEC 60332-3-24; IEC 61034-2; IEC 60754 series where applicable | Check cable bundle diameter, test category, tray loading, minimum bending radius, and derating caused by grouping |
| High-rise buildings and escape routes | Typically 300/500 V, 450/750 V, or 0.6/1 kV, selected according to the circuit and local regulations | Low-smoke, halogen-free cable with enhanced flame-spread performance; use fire-resistant cable when circuit operation must continue during a fire | Low smoke, low acidity and low corrosivity are important for evacuation and protection of electronic equipment; flame retardance alone does not ensure circuit integrity | IEC 60332-3; IEC 60754-1; IEC 60754-2; IEC 61034-2; EN 50575 where Construction Products Regulation classification applies | Separate ordinary flame-retardant requirements from fire-resistance requirements such as circuit integrity, duration, and supporting-system testing |
| Data centers and telecommunications rooms | Often extra-low-voltage, 300/500 V, or 0.6/1 kV auxiliary and power circuits | Low-smoke, halogen-free screened or unscreened cable; select solid or stranded conductors according to termination and flexibility requirements | Prioritize low smoke, low corrosive gas, controlled flame spread, and compatibility with dense cable routing | IEC 60332-1-2 or IEC 60332-3; IEC 60754-1/-2; IEC 61034-2; applicable structured-cabling standards for communication cables | Check shielding effectiveness, signal bandwidth, heat accumulation, cable-tray fill, bend radius, and separation from power circuits |
| Industrial plants and manufacturing facilities | Commonly 0.6/1 kV for power distribution; higher voltage ratings may be required for medium-voltage systems | Flame-retardant thermoset or thermoplastic insulation; armoured, screened, oil-resistant, or chemically resistant construction may be needed | Flame spread should be limited across cable groups; smoke and gas requirements depend on occupancy, process hazards, and local code | IEC 60332-3; IEC 60754 and IEC 61034 where specified; IEC 60502-1 for many low-voltage power cable designs | Evaluate continuous and short-circuit temperature, chemical exposure, impact, vibration, oil, UV, moisture, and installation conditions |
| Public transport, tunnels, and underground facilities | Usually 0.6/1 kV for auxiliary and distribution circuits, with system-specific ratings for traction and signaling | Low-smoke, halogen-free, mechanically protected cable; fire-resistant designs may be required for emergency, communication, lighting, or control circuits | Very low smoke and low corrosive gas are critical in confined spaces; flame retardance and circuit integrity must be specified separately | IEC 60332 series; IEC 60754 series; IEC 61034-2; project-specific rail, tunnel, or transit fire-performance standards | Confirm emergency operating time, fire-resistance test duration, mechanical protection, water exposure, and authority approval requirements |
| Marine and offshore installations | Voltage depends on the vessel or platform distribution system; 0.6/1 kV is common for many low-voltage circuits | Marine-grade low-smoke, halogen-free cable with resistance to moisture, oil, vibration, and salt-laden environments | Controlled flame spread, low smoke, and low halogen acid gas reduce risk in enclosed accommodation and machinery spaces | IEC 60332 series; IEC 60754 series; IEC 61034-2; applicable marine certification and installation rules | Check fire-resistant circuit requirements, bending and vibration performance, water resistance, armour, shielding, and approval documentation |
| Outdoor, solar, and renewable-energy systems | System voltage may include 600 V, 1,000 V, or 1,500 V DC in photovoltaic applications; select the cable rating for the complete system | UV-resistant, weather-resistant, flame-retardant cable with insulation suitable for outdoor DC operation and expected thermal cycling | Flame performance should be combined with resistance to UV, ozone, moisture, and temperature cycling; a flame test does not prove outdoor durability | IEC 60332 where specified; application-specific photovoltaic or energy-cable standards; IEC 60216 principles for thermal ageing evaluation | Check maximum DC voltage, conductor ampacity, installation temperature, UV exposure, wet location rating, connector compatibility, and routing |
| Control, instrumentation, and safety systems | Often extra-low-voltage or 300/500 V; power, signal, and emergency circuits may require different ratings | Small-core multicore cable, individually screened pairs, overall shield, armoured construction, or fire-resistant construction as required by the system | Select flame retardance for the installation density; use low-smoke and fire-resistant designs when signals must remain available during a fire | IEC 60332 series; IEC 60754 and IEC 61034 where specified; relevant instrumentation, alarm, emergency, or control-system standards | Verify electrical noise immunity, capacitance, impedance, pair identification, circuit integrity, segregation, and compatibility with terminals |